ActiCarb

A metal 4V cell type molecular filter with highly engineered leak free design, filled with specific activated carbon for toxic, radioactive gases removal. Ideal for nuclear, defense, research, biosafety, healthcare applications.

  • Individual test of the leak rate
  • Individual certificate
  • Compatible with BIBO (Bag In Bag Out) housings
  • Molecular filter for dangerous gases
  • High filter efficiency
  • ICON6 Molecular
Item Type Pollutant Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa) Optimum RH (%)
ActiCarb Nuclear ICH3 610 610 292 1200 300 ≤ 40
ActiCarb Nuclear ICH3 305 610 292 600 300 ≤ 40
ActiCarb Medical Iodine 131 610 610 292 1200 140 ≤ 40
ActiCarb Medical Iodine 131 305 610 292 600 140 ≤ 40
ActiCarb Mercury Mercury 610 610 292 800 100 ≤ 40
ActiCarb Mercury Mercury 305 610 292 400 100 ≤ 40
ActiCarb VOC VOC 610 610 292 1800 300 ≤ 50
ActiCarb VOC VOC 305 610 292 900 300 ≤ 50
ActiCarb Basic Basic gas 610 610 292 1200 200 ≤ 90
ActiCarb Basic Basic gas 305 610 292 600 200 ≤ 90
ActiCarb Acid Acid gas 610 610 292 1200 200 ≤ 90
ActiCarb Acid Acid gas 305 610 292 600 200 ≤ 90
ActiCarb ABEK War gas 610 610 292 500 420 ≤ 90
ActiCarb ABEK War gas 305 610 292 250 420 ≤ 90

Specifications

Application
Acticarb- ABEK: Defense, Civil and military protection. -MERCURY: Research laboratories and production units for lamps and batteries. - ACID: Nuclear or other industries where hydrogen fluoride needs to be captured. - BASIC: Animal or research laboratories to capture ammonia. - VOC: When BIBO (Bag in Bag Out) is required to proceed to the VOC filter change. - NUCLEAR: Nuclear industry, electricity production or research. - MEDICAL: Hospitals with particle accelerator (cyclotron)
Filter Frame
Stainless steel, Galvanised steel
Gasket
½ round 15 mm moulded neoprene foam
Comment
Media: 50 mm (2 inch) bed depth of Campure 8, high quality media; vibrated and tamped to meet leakage requirements
Gas to trap: Formaldehyde, Acetoldehyde
Impregnate: CamPure 8, Aluminium Impreg. KMn04
Relative Humidity: < 90%
Temperature: 80°C maximum continues
Controls: Individual test run for leakages (< 2,5 x 10-4) and pressure drop