To meet increasing demands for performance, Camfil has developed the CamGT 3V-440 high efficiency air filter. The result is a high-performing hydrophobic air filter that offers excellent gas turbine protection, decreases maintenance, and reduces carbon footprint with EPA filters. It is suitable for all installations where safety/reliability is important, including corrosive/humid/wet conditions.
Item Type | ISO 29461 | ISO rating ISO 16890 | Filter Class ASHRAE | Width (mm) | Height (mm) | Depth (mm) | Airflow (m3/h) | Pressure drop Initial (Pa) |
---|---|---|---|---|---|---|---|---|
CamGT 3V-440-T8 | T8 | ePM1 70% | MERV 14 | 592 | 592 | 440 | 4250 | 105 |
CamGT 3V-440-T9 | T9 | ePM1 85% | MERV 15 | 592 | 592 | 440 | 4250 | 120 |
CamGT 3V-440-T10 | T10 | 592 | 592 | 440 | 4250 | 155 | ||
CamGT 3V-440-T11A | T11 | 592 | 592 | 440 | 4250 | 175 | ||
CamGT 3V-440-T12 | T12 | 592 | 592 | 440 | 4250 | 310 |
For several years, Hornsgatan has been designated Sweden's dirtiest street when it comes to air pollution. Hornsgatan is an exposed street when it comes to harmful particles in the air. How does this affect residents?
Air quality Case studiesThe CamGT air filter line has been turbo-boosted to maximize power, profits, and uptime of your gas turbine.
Energy and Power SystemsPlant located in the Gulf Coast of Louisiana upgrades to the Cam-Flo pocket air filters and CamGT 4V-300 EPA E10 filters after tests show lower pressure drop, lower engine degradation, and signifcant savings as a result of filtration.
Manufacturing and machinery Case studies Energy and Power Systems
A leading steel producer upgraded blower filtration, extending final filter life by 16x, pre-filter life by 4x, and achieving 100% operational availability.
Hi-Flo bag air filters and CamGT EPA air filter upgrade reduces compressor efficiency degradation by over 80%, slashes 3 offline filter replacements, 7 online prefilter replacements, and 3 offline water washes per year.
CamGT 3V-600 static final filters and Cam-Flo GT Hybrid pocket air filters eliminate 6 offline washes per year, improve gas turbine compressor efficiency, and boost power output for a Singaporean coastal cogeneration power plant.
Located offshore Ivory Coast, Africa, the CamGT EPA filter solution saves Foxtrot International 3 shutdowns per year and eliminates salt corrrosion, without compromising on footprint.
Learn how The Value Rating, the easiest way to select air filters for gas turbines, works.
Hot corrosion is a source of nonrecoverable degradation on gas turbines. It is a chemical reaction between salts, sulfur and heat, where the damages can reduce an engine’s life by up to 75%. One of the most effective methods is to eliminate the contaminants triggering the chemical reaction. This paper examines the causes of hot corrosion and assesses various methods of mitigation.
An energy plant on the pacific coast upgrades their Siemens 501F gas turbine filtration to the CamGT 4V-300 air intake filters after tests show its water and salt handling capabilities.
Air sampling, CamLab on-site analysis, as well as a Life Cycle Cost analysis show that the CamGT EPA filters will result in no shutdowns for turbine water washes, final filter shutdown extended to 5 years, decreased risk of corrosion and maximum power output.
Frequent pressure and short filter replacement intervals led to high operational costs. Camfil's Cam-Flo air intake pre-filters and CamGT EPA air filters met their goal of 8000 hours of life and reduced pressure drop by 50%.
Manufacturing and machinery Case studies Energy and Power Systems
With a growing demand for greener practices, and rising operational costs, it has become imperative that gas turbine operators cut their carbon footprints. Upgraded air intake systems are one of the easiest, most cost-effective ways to meet these demands, while improving operations at the same time.
To answer this question, let's look at the difference between a land based gas turbine and a jet engine.
Camfil designs a static EPA retrofit gas turbine filtration solution for LM6000 turbines to ensure they deliver reliable power & heating to the district. The result of the upgrade was 3x more filter life, reduction in CO2 emissions by 1 100 tons per year, and fuel consumption savings of 650 000 Sm3 per year.
If you are looking to expand your knowledge on the impact of air filtration on your gas turbines and other turbomachinery, look no more!
Upgrade your gas turbine air inlet filters to cut carbon emissions per MWh produced.
Noise complaints from neighboring communities in Thailand prompted the plants to evaluate a noise-reducing filtration system. The CamGT high efficiency air filter solution not only improved the noise levels, it also increased turbine availability, improved pressure drop and helped the gas turbine produce more power.
Tata Power Ltd, India's largest integrated power company requests Camfil for a Cam-Flo pocket bag filter and CamGT static air filter retrofit after heavy hot corrosion in the gas turbine and high pressure drop jeopardized performance and safety.
Dalkia, a leader in the French gas turbine market, launched a national comparative test for various air intake filters, including Camfil's Hi-Flo pre-filters and CamGT EPA filters, to increase power production for their 10 GE LM6000 gas turbines.
The test rig has been calibrated according to standards EN 779, ISO 16890 and ASHRAE 52.2 and was developed for air filter testing simulating the harsh climate conditions where gas turbines are often located.