Item Type ISO/PM rating Filter Class EN779 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa) Energy (kWh/year) Energy Class (Eurovent)
A5 ePM10 60% M5 592 592 600 3400 45 748 C
B5 ePM10 60% M5 490 592 600 2800 45 C
C5 ePM10 60% M5 287 592 600 1700 45 C
A6 ePM2,5 50% M6 592 592 600 3400 70 1189 C
B6 ePM2,5 50% M6 490 592 600 2800 70 C
C6 ePM2,5 50% M6 287 592 600 1700 70 C
UF6 ePM2,5 50% M6 592 592 600 3400 60 872 B
UG6 ePM2,5 50% M6 490 592 600 2800 55 B
UH6 ePM2,5 50% M6 287 592 600 1700 60 B
3UF6 ePM2,5 50% M6 490 490 600 2334 70 B
A7 ePM1 60% F7 592 592 600 3400 95 1337 C
B7 ePM1 60% F7 490 592 600 2800 95 C
C7 ePM1 60% F7 287 592 600 1700 95 C
UF7 ePM1 60% F7 592 592 600 3400 75 940 A
UG7 ePM1 60% F7 490 592 600 2800 75 A
UH7 ePM1 60% F7 287 592 600 1700 75 A
A8 ePM1 70% F8 592 592 600 3400 160
B8 ePM1 70% F8 490 592 600 2800 160
C8 ePM1 70% F8 287 592 600 1700 160
3UF9 ePM1 85% F9 490 490 600 2334 145
3UF8 ePM1 70% F8 490 490 600 2334 145
UF9 ePM1 85% F9 592 592 600 3400 160 1956 D
UG9 ePM1 85% F9 490 592 600 2800 160 D
UH9 ePM1 85% F9 287 592 600 1700 160 D
UF8 ePM1 70% F8 592 592 600 3400 145
UG8 ePM1 70% F8 490 592 600 2800 145
UH8 ePM1 70% F8 287 592 600 1700 145
 Pressure drop calculation tool is available

Calculate pressure drop

Choose a full-size filter module in the table above to calculate the pressure drop.
Full-size filter modules are typically 592x592mm for bag/panel filters and 610x610mm for HEPA filters.

Specifications

Application
Comfort air conditioning applications, pre filter applications
Frame
Galvanised steel
Media
Glass fiber
Max temperature (°C)
70°C
Relative Humidity
100%
Dimension standard
Filter front dimensions according EN 15805
Installation options
Front and side access housings and frames are available
Max Airflow
1,25 x nominal flow

Articles related to Hi-Flo

Camfil ProSafe 

Some processes are more sensitive than others. If you work in the food and beverage or life science industries, you know how tough the demands on clean air are. To be sure you have the right filter, look for the ProSafe symbol.

Food and beverage

Odour Exasperation - Here is what you can do in your restaurant to eliminate odour nuisance & neutralize the air

Restaurants have odours coming from a variety of sources and they all have one thing in common, they spread 'air pollution'. Odours are one of the leading causes of air pollution at restaurants or food courts and the odour profile from a kitchen depends on

Air quality Commercial and Public buildings Food and beverage

GLOBAL FAST FOOD RESTAURANT is using dynamic clean air solutions in china

Fast food stores are usually located in a crowded commercial area or building where there are problems such as polluted air, gases, and odours. The fresh air fan units in the ventilation system are often close to the pollution source, i.e., exhaust air of other shops in the building.

Commercial and Public buildings Case Studies

Dalkia Power Generation

Case Study: Dalkia, a leader in the French gas turbine market, launched a national comparative test to increase power production by improving air filtration efficiency.

Energy and Power Systems Case Studies

Dalkia Upgrades To EPA Class

Case Study: Camfil Wins Dalkia Over Four Competitors. Dalkia designed 12 testing benches to compare four air filtration combinations on three sites in France with different operating environments. Four competitors were free to select their best combinations.

Energy and Power Systems Case Studies

Norland Managed Services

Case Study: Indoor Air Quality Worth The Investment. This major bank is one of the world‘s largest financial institutions. Norland Managed services are the Facilities Management provider for their 600,000 square feet London office building, in central London.

Commercial and Public buildings Case Studies

Camfil Serves Up Savings in Energy, Filter Costs, and Labour

Case Study: Filter Savings At Frozen Food Manufacturer. Three air handling units supplied air to critical processing areas in one of the USA's largest frozen food manufacturing facilities. The pre and final filter combination saved the plant over $33,000 per year.

Case Studies Food and beverage

Call Kuala Lumpur Office
+603 8023 8250
Call Penang Office
+604 642 5004
Find a contact