Hi-Cap

  • Optimized media surface with conical pocket shape
  • Easy installation
  • Robust construction
  • Robust metal header frame
  • High dust holding capacity
  • ICON7 iso16890.ai
  • ICON31 Mount_bagfilters
Item Type ISO 16890 Filter Class EN779 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa)
HC66/360 Coarse 60% G4 592 592 360 3400 40
HC56/360 Coarse 60% G4 490 592 360 2800 40
HC36/360 Coarse 60% G4 287 592 360 1700 40
HC33/360 Coarse 60% G4 287 287 360 800 40
HC63/360 Coarse 60% G4 592 287 360 1700 40
HC66/580 Coarse 60% G4 592 592 580 3400 30
HC56/580 Coarse 60% G4 490 592 580 2800 30
HC36/580 Coarse 60% G4 287 592 580 1700 30
HC33/580 Coarse 60% G4 287 287 580 850 30
HC63/580 Coarse 60% G4 592 287 580 1700 30
 Pressure drop calculation tool is available

Calculate pressure drop

Choose a full-size filter module in the table above to calculate the pressure drop.
Full-size filter modules are typically 592x592mm for bag/panel filters and 610x610mm for HEPA filters.

Specifications

Application
Prefilter for air conditioning and ventilation systems
Frame
Galvanised steel
Media
Synthetic
Max temperature °C
70°C
Relative Humidity
100%
Max final pressure drop, EN 13053
Initial pressure drop + 50 Pa or initial pressure drop x3 (whichever is lower)
Dimension standard
Filter front dimensions according EN 15805
Installation options
Front and side access housings and frames are available
Max Airflow
1,25 x nominal flow

Hospitals & Healthcare: St. James Hospital Dublin

Case Study: St James Hospital Prevents Aspergillus. Healthcare facilities must maintain the highest levels of cleanliness to promote health and healing. Camfil provides air cleaners for these environments. St. James Hospitaal in Dublin used Camfil for Aspergillus prevention.

Case Studies

Tata Power Trombay Retrofit

Case Study: Retrofit Solutions For Tata Power Ltd. Based on the site survey, Camfil proposed replacement of the pulse filter system with a three-stage static/barrier filter system, considering the local environment filled with refineries and a thermal power plant nearby.

Case Studies

UNIVERSITY SEES PROOF OF 24% LOWER ANNUAL ENERGY COSTS USING CAMFIL FILTER VS COMPETING FILTER

Case Study: Energy Savings At Western United States University. A Life Cycle Costing (LCC) analysis proved the Camfil Durafil filter operated at a 24% lower energy cost per year than the Viledon T-60. The Camfil product would save the customer $14 per filter per year versus the alternative.

Case Studies

Let Camfil be your clean air partner. Contact us today!
Call Dublin Now
+353 1 8484977
Find a contact