Hi-Flo ProSafe

  • Specially designed for process safety (Food & Life Science applications)
  • Very low initial pressure drop
  • Very flat pressure drop curve
  • Moulded, rigid and aerodynamically shaped plastic frame
  • Food Compliant - EC 1935:2004
  • Anti-microbial gowth certified -( ISO846- VDI6022)
  • ICON3 efficiency guarantee
  • ICON7 iso16890.ai
  • ICON32 Aplus
  • ICON20 prosafe
  • ICON23 Eurovent_no_abc
  • ICON31 Mount_bagfilters
Item Type ISO 16890 Filter Class EN779 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa) Energy (kWh/year) Energy Class (Eurovent)
7/670 ePM1 60% F7 287 287 670 800 65 A+
6/640 ePM2,5 50% M6 592 592 640 3400 55 748 A
6/640 ePM2,5 50% M6 490 592 640 2700 55 A
6/640 ePM2,5 50% M6 287 592 640 1700 55 A
6/640 ePM2,5 50% M6 592 490 640 2700 55 A
6/640 ePM2,5 50% M6 490 490 640 2330 55 A
6/640 ePM2,5 50% M6 592 287 640 1700 55 A
6/640 ePM2,5 50% M6 287 287 640 800 55 A
6/520 ePM2,5 50% M6 592 592 520 3400 60 929 B
6/520 ePM2,5 50% M6 490 592 520 2700 60 B
6/520 ePM2,5 50% M6 287 592 520 1700 60 B
6/520 ePM2,5 50% M6 592 490 520 2700 60 B
6/520 ePM2,5 50% M6 490 490 520 2330 60 B
6/520 ePM2,5 50% M6 592 287 520 1700 60 B
6/520 ePM2,5 50% M6 287 287 520 800 60 B
6/370 ePM2,5 50% M6 592 592 370 3400 70 1405 D
6/370 ePM2,5 50% M6 490 592 370 2700 70 D
6/370 ePM2,5 50% M6 287 592 370 1700 70 D
6/370 ePM2,5 50% M6 592 490 370 2700 70 D
6/370 ePM2,5 50% M6 490 490 370 2330 70 D
6/370 ePM2,5 50% M6 592 287 370 1700 70 D
6/370 ePM2,5 50% M6 287 287 370 800 70 D
7/670 ePM1 60% F7 592 592 670 3400 65 838 A+
7/670 ePM1 60% F7 490 592 670 2700 65 A+
7/670 ePM1 60% F7 287 592 670 1700 65 A+
7/670 ePM1 60% F7 592 490 670 2700 65 A+
7/670 ePM1 60% F7 490 490 670 2330 65 A+
7/670 ePM1 60% F7 592 287 670 1700 65 A+
7/640 ePM1 60% F7 592 592 640 3400 70 918 A
7/640 ePM1 60% F7 490 592 640 2700 70 A
7/640 ePM1 60% F7 287 592 640 1700 70 A
7/640 ePM1 60% F7 592 490 640 2700 70 A
7/640 ePM1 60% F7 490 490 640 2330 70 A
7/640 ePM1 60% F7 592 287 640 1700 70 A
7/640 ePM1 60% F7 287 287 640 800 70 A
7/520 ePM1 60% F7 592 592 520 3400 75 1031 B
7/520 ePM1 60% F7 490 592 520 2700 75 B
7/520 ePM1 60% F7 287 592 520 1700 75 B
7/520 ePM1 60% F7 592 490 520 2700 75 B
7/520 ePM1 60% F7 490 490 520 2330 75 B
7/520 ePM1 60% F7 592 287 520 1700 75 B
7/520 ePM1 60% F7 287 287 520 800 75 B
7/370 ePM1 60% F7 592 592 370 3400 90 1643 D
7/370 ePM1 60% F7 490 592 370 2700 90 D
7/370 ePM1 60% F7 287 592 370 1700 90 D
7/370 ePM1 60% F7 592 490 370 2700 90 D
7/370 ePM1 60% F7 490 490 370 2330 90 D
7/370 ePM1 60% F7 592 287 370 1700 90 D
7/370 ePM1 60% F7 287 287 370 800 90 D
9/640 ePM1 85% F9 592 592 640 3400 115 1474 C
9/640 ePM1 85% F9 490 592 640 2700 115 C
9/640 ePM1 85% F9 287 592 640 1700 115 C
9/640 ePM1 85% F9 592 490 640 2700 115 C
9/640 ePM1 85% F9 490 490 640 2330 115 C
9/640 ePM1 85% F9 592 287 640 1700 115 C
9/640 ePM1 85% F9 287 287 640 800 115 C
9/520 ePM1 85% F9 592 592 520 3400 165 2091 D
9/520 ePM1 85% F9 490 592 520 2700 165 D
9/520 ePM1 85% F9 287 592 520 1700 165 D
9/520 ePM1 85% F9 592 490 520 2700 165 D
9/520 ePM1 85% F9 490 490 520 2330 165 D
9/520 ePM1 85% F9 592 287 520 1700 165 D
9/520 ePM1 85% F9 287 287 520 800 165 D
 Pressure drop calculation tool is available

Calculate pressure drop

Choose a full-size filter module in the table above to calculate the pressure drop.
Full-size filter modules are typically 592x592mm for bag/panel filters and 610x610mm for HEPA filters.

Video

Specifications

Application
Air conditioning applications and as pre filters for clean rooms
Frame
Plastic
Media
Glass fiber
Max temperature (°C)
70ºC
Relative Humidity
100%
Max final pressure drop, EN 13053
Initial pressure drop + 100 Pa or initial pressure drop x3 (whichever is lower)
Dimension standard
Filter front dimensions according EN 15805
Installation options
Front and side access housings and frames are available
Max Airflow
1,25 x nominal flow

Related Products

Articles related to Hi-Flo

Prosafe promobox

Camfil ProSafe 

Some processes are more sensitive than others. If you work in the food and beverage or life science industries, you know how tough the demands on clean air are. To be sure you have the right filter, look for the ProSafe symbol.

Food and beverage
burger_restaurant-unsplash.jpg

GLOBAL FAST FOOD RESTAURANT is using dynamic clean air solutions in china

Fast food stores are usually located in a crowded commercial area or building where there are problems such as polluted air, gases, and odours. The fresh air fan units in the ventilation system are often close to the pollution source, i.e., exhaust air of other shops in the building.

Case Studies Commercial and Public buildings

Dalkia Power Generation

Case Study: Dalkia, a leader in the French gas turbine market, launched a national comparative test to increase power production by improving air filtration efficiency.

Case Studies Energy and Power Systems

EGAT North Power Generation

Case Study: EGAT North shifted to Camfil Filters and saved $1.4M USD in Yearly Power Degradation.

Case Studies Energy and Power Systems

Dalkia Upgrades To EPA Class

Case Study: Camfil Wins Dalkia Over Four Competitors. Dalkia designed 12 testing benches to compare four air filtration combinations on three sites in France with different operating environments. Four competitors were free to select their best combinations.

Case Studies Energy and Power Systems

Norland Managed Services

Case Study: Indoor Air Quality Worth The Investment. This major bank is one of the world‘s largest financial institutions. Norland Managed services are the Facilities Management provider for their 600,000 square feet London office building, in central London.

Case Studies Commercial and Public buildings

Camfil Serves Up Savings in Energy, Filter Costs, and Labour

Case Study: Filter Savings At Frozen Food Manufacturer. Three air handling units supplied air to critical processing areas in one of the USA's largest frozen food manufacturing facilities. The pre and final filter combination saved the plant over $33,000 per year.

Case Studies Food and beverage