A compact, refillable, corrosion resistant V-cell molecular filter filled with Camfil activated alumina or activated carbon. They are ideal for corrosion control applications versatile gas phase air filter installed in supply, recirculation, and exhaust air systems in commercial, industrial, and process applications. Their design provides the best total cost of ownership for the removal of corrosive, odorous, and irritant gases.
Item Type | Width (mm) | Height (mm) | Depth (mm) | Pressure drop (Pa) | Nominal weight (kg) | Nominal weight (lbs) | Optimum RH (%) | Optimum temperature (°C) | Optimum temperature (°F) |
---|---|---|---|---|---|---|---|---|---|
CamCarb VG300 SO2_H2S^³ | 300 | 300 | 300 | 315 | 14.5 | 32.0 | 40 - 90 | 10 - 60 | 50 - 140 |
CamCarb VG300 Acids_H2S^³ | 300 | 300 | 300 | 315 | 14.5 | 32.0 | 40 - 90 | 10 - 60 | 50 - 140 |
CamCarb VG300 VOC | 300 | 300 | 300 | 500 | 10.0 | 22.0 | 0 - 70 | Max. 40 | Max. 104 |
CamCarb VG300 H2S_Mercaptans | 300 | 300 | 300 | 500 | 10.0 | 22.0 | 40 - 90 | 10 - 60 | 50 - 140 |
CamCarb VG300 Acids | 300 | 300 | 300 | 500 | 10.0 | 22.0 | 40 - 90 | 10 - 60 | 50 - 140 |
CamCarb VG300 VOC_O3_Acid_H2S | 300 | 300 | 300 | 440 | 11.7 | 25.8 | 40 - 70 | 10 - 40 | 50 - 104 |
CamCarb VG300 VOC_O3_NO2_SO2 | 300 | 300 | 300 | 560 | 8.8 | 19.4 | 0 - 70 | Max. 40 | Max. 104 |
CamCarb VG300 Bases | 300 | 300 | 300 | 500 | 10.0 | 22.0 | 40 - 90 | 10 - 40 | 50 - 104 |
CamCarb VG440 SO2_H2S^³ | 300 | 150 | 440 | 94 | 6.5 | 14.3 | 40 - 90 | 10 - 60 | 50 - 140 |
CamCarb VG440 Acids_H2S^³ | 300 | 150 | 440 | 94 | 6.5 | 14.3 | 40 - 90 | 10 - 60 | 50 - 140 |
CamCarb VG440 VOC | 300 | 150 | 440 | 146 | 4.5 | 10.0 | 0 - 70 | Max. 40 | Max. 104 |
CamCarb VG440 H2S_Mercaptans | 300 | 150 | 440 | 146 | 4.5 | 10.0 | 40 - 90 | 10 - 60 | 50 - 140 |
CamCarb VG440 Acids | 300 | 150 | 440 | 146 | 4.5 | 10.0 | 40 - 90 | 10 - 60 | 50 - 140 |
CamCarb VG440 VOC_O3_Acid_H2S | 300 | 150 | 440 | 120 | 5.6 | 12.5 | 40 - 70 | 10 - 40 | 50 - 104 |
CamCarb VG440 VOC_O3_NO2_SO2 | 300 | 150 | 440 | 142 | 4.7 | 10.3 | 0 - 70 | Max. 40 | Max. 104 |
CamCarb VG440 Bases | 300 | 150 | 440 | 146 | 4.5 | 10.0 | 40 - 90 | 10 - 40 | 50 - 104 |
The biogas process is critical as it releases heavily contaminated gasses that can cause engine corrosion and equipment abrasion, causing unscheduled downtime for maintenance and repair, which results in loss of output and profit. Luckily, there are several ways of solving molecular filtration in biogas plants with different types of filter media in deep beds.
Energy and Power SystemsCamCarb VG modules with loose-fill media are robust solutions suited for make-up air (outdoor air) and recirculation air systems. The primary use is the control of acidic gases that are responsible for the corrosion of electronics and electrical equipment in heavy process industries such as pulp and paper mills, petrochemical refineries, mining and metal refining operations, and wastewater treatment plants.
Electronics and optics Life science and healthcare Manufacturing and Machinery Air quality Commercial and Public buildingsCamfil CC2000 Air Purifiers Improve IAQ at Refresco Italy
Corrosion of electronic process control equipment can cause disruptions in production leading to lower productivity and lower profitability - this can be expensive to fix.