ActiCarb

  • Used in Nuclear, Research, Life Science, Healthcare and Defense sector
  • Removes airborne molecules such as odors, irritants, toxic and corrosive gases
  • Depending on which gas should be trapped the ideal carbon grade and impregnation is selected
  • Individual test of the leak rate
  • Individual certificate
  • ICON6 Molecular
Item Type Pollutant Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa) Optimum RH (%)
ActiCarb Medical Iodine 131 610 610 292 1200 300 ≤ 40
ActiCarb Medical Iodine 131 305 610 292 600 300 ≤ 40
ActiCarb Nuclear ICH3 610 610 292 1200 300 ≤ 90
ActiCarb Nuclear ICH3 305 610 292 600 300 ≤ 90
ActiCarb Mercury Mercury 305 610 292 400 100 ≤ 40
ActiCarb VOC VOC 610 610 292 1800 300 ≤ 50
ActiCarb VOC VOC 305 610 292 900 300 ≤ 50
ActiCarb Basic Basic gas 610 610 292 1200 200 ≤ 90
ActiCarb Basic Basic gas 305 610 292 600 200 ≤ 90
ActiCarb Acid Acid gas 610 610 292 1200 200 ≤ 90
ActiCarb Acid Acid gas 305 610 292 600 200 ≤ 90
ActiCarb ABEK War gas 305 610 292 250 420 ≤ 90

Specifications

Application
Acticarb- ABEK: Defense, Civil and military protection. -MERCURY: Research laboratories and production units for lamps and batteries. - ACID: Nuclear or other industries where hydrogen fluoride needs to be captured. - BASIC: Animal or research laboratories to capture ammonia. - VOC: When BIBO (Bag in Bag Out) is required to proceed to the VOC filter change. - NUCLEAR: Nuclear industry, electricity production or research. - MEDICAL: Hospitals with particle accelerator (cyclotron)
Filter Frame
Stainless steel, Galvanised steel
Gasket
½ round 15 mm moulded neoprene foam
Comment
Media: 50 mm (2 inch) bed depth of Campure 8, high quality media; vibrated and tamped to meet leakage requirements
Gas to trap: Formaldehyde, Acetoldehyde
Impregnate: CamPure 8, Aluminium Impreg. KMn04
Relative Humidity: < 90%
Temperature: 80°C maximum continues
Controls: Individual test run for leakages (< 2,5 x 10-4) and pressure drop

Articles related to Acticarb

Gaining control over corrosion with molecular air filtration solutions

Corrosion of electronic process control equipment can cause disruptions in production leading to lower productivity and lower profitability - this can be expensive to fix.

Electronics and optics
Call Kuala Lumpur Office
+603 8023 8250
Call Penang Office
+604 642 5004
Find a contact