Opakfil 2V

  • Light and robust
  • ICON3 efficiency guarantee
  • ICON7 iso16890.ai
  • ICON23 Eurovent_no_abc
Item Type ISO/PM rating Filter Class EN779 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa) Energy (kWh/year) Energy Class (Eurovent)
OPGP-M6-0592/0592/0268-2V-20-00 ePM10 70% M6 592 592 268 3400 85 E
OPGP-M6-0592/0490/0268-2V-20-00 ePM10 70% M6 592 490 268 2800 85 E
OPGP-M6-0592/0287/0268-2V-20-00 ePM10 70% M6 592 287 268 1700 85 E
OPGP-F7-0592/0490/0268-2V-20-00 ePM1 55% F7 592 490 268 2800 100 C
OPGP-F7-0592/0287/0268-2V-20-00 ePM1 55% F7 592 287 268 1700 100 C
OPGP-F8-0592/0592/0268-2V-20-00 ePM1 70% F8 592 592 268 3400 120 E
OPGP-F8-0592/0490/0268-2V-20-00 ePM1 70% F8 592 490 268 2800 120 E
OPGP-F8-0592/0287/0268-2V-20-00 ePM1 70% F8 592 287 268 1700 120 E
OPGP-F9-0592/0592/0268-2V-20-00 ePM1 80% F9 592 592 268 3400 180 E
OPGP-F9-0592/0490/0268-2V-20-00 ePM1 80% F9 592 490 268 2800 180 E
OPGP-F9-0592/0287/0268-2V-20-00 ePM1 80% F9 592 287 268 1700 180 E
OPGP-F7-0592/0592/0268-2V-20-00 ePM1 55% F7 592 592 268 3400 100 1359 C

Specifications

Application
Air conditioning applications and preparatory filtration in clean rooms
Frame
ABS
Media
Glass fiber
Max temperature °C
70ÂșC
Relative Humidity
100%
Separator
Hot-melt
Sealant
Polyurethane
Dimension standard
Filter front dimensions according EN 15805
Installation options
Front and side access housings and frames are available
Max Airflow
1,25 x nominal flow