Hi-Flo M, P, TM

  • Large surface area
  • Save energy - optimised design (LCC)
  • Comprehensive range of standard sizes
  • Innovative pocket design for optimum air distribution
  • Conical pockets
  • Certified performance
  • ICON2 eurovent energy efficiency class
  • ICON3 efficiency guarantee
  • ICON7 ISO16890.ai
  • ICON8
  • ICON32 Aplus
  • ICON31 Mount_bagfilters
  • ICON44 SGBC_
ISO rating ISO 16890 Filter Class EN779 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa) Energy (kWh/year) Energy Class
ePM2,5 50% M6 490 592 640 2800 55 A
ePM2,5 50% M6 592 592 640 3400 55 748 A
ePM2,5 50% M6 287 592 640 1700 55 A
ePM1 85% F9 592 592 640 3400 130 1722 C
ePM1 85% F9 490 592 640 2800 130 C
ePM1 85% F9 287 592 640 1700 130 C
ePM1 60% F7 490 592 640 2800 60 A+
ePM1 60% F7 592 592 640 3400 60 838 A+
ePM1 60% F7 287 592 640 1700 60 A+
ePM2,5 50% M6 592 592 520 3400 60 986 C
ePM2,5 50% M6 490 592 520 2800 60 C
ePM2,5 50% M6 287 592 520 1700 60 C
ePM1 85% F9 490 592 520 2800 160 D
ePM1 85% F9 592 592 520 3400 160 2016 D
ePM1 85% F9 287 592 520 1700 160 D
ePM1 60% F7 592 592 520 3400 75 895 A
ePM1 60% F7 490 592 520 2800 75 A
ePM1 60% F7 287 592 520 1700 75 A
ePM2,5 50% M6 287 592 370 1700 70 C
ePM2,5 50% M6 490 592 370 2800 70 C
ePM2,5 50% M6 592 592 370 3400 70 1280 C
ePM1 60% F7 592 592 370 3400 95 1427 C
ePM1 60% F7 490 592 370 2800 95 C
ePM1 70% F8 592 592 640 3400 130
ePM1 70% F8 490 592 640 2800 130
ePM1 70% F8 287 592 640 1700 130
ePM1 70% F8 592 592 370 3400 205
ePM1 70% F8 490 592 370 2800 205
ePM1 70% F8 287 592 370 1700 205
ePM1 70% F8 592 592 520 3400 160
ePM1 70% F8 490 592 520 2800 160
ePM1 70% F8 287 592 520 1700 160
 Pressure drop calculation tool is available

Calculate pressure drop

Choose a full-size filter module in the table above to calculate the pressure drop.
Full-size filter modules are typically 592x592mm for bag/panel filters and 610x610mm for HEPA filters.

Specifications

Application
Air conditioning applications
Frame
Galvanised steel
Media
Glass fiber
Max temperature °C
70°C
Relative Humidity
100%
Recommended final pressure drop, EN 13053
M6-F7: 200 Pa, F9: 300 Pa
Dimension standard
Filter front dimensions according EN 15805
Installation options
Front and side access housings and frames are available
Call Auckland Office
+64 9 636 0663
Call Cambridge Office
+64 7 827 4142
Find a contact