Airopac Traditional HF

  • Low pressure drop
  • Robust metal header frame
  • Large surface area
  • Rigid design concept
  • High dust holding capacity
Item Type ISO 16890 Filter Class EN779 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa)
3CPMHF-242412-60 ePM2,5 50% M6 592 592 292 2500 60
3CPMHF-122412-60 ePM2,5 50% M6 287 592 292 1250 60
3CPMHF-242412-90 ePM1 55% F7 592 592 292 2500 95
3CPMHF-122412-90 ePM1 55% F7 287 592 292 1250 95
3CPMHF-242412-95 ePM1 80% F9 592 592 292 1800 80
3CPMHF-122412-95 ePM1 80% F9 287 592 292 900 80

Specifications

Application
Air conditioning applications and preparatory filtration in clean-rooms
Frame
Galvanised steel
Media
Glass fiber
Max temperature °C
110ºC
Relative Humidity
100%
Max final pressure drop, EN 13053
Initial pressure drop + 100 Pa or initial pressure drop x3 (whichever is lower)
Separator
Aluminium
Gasket
Polyurethane
Sealant
Polyurethane
Dimension standard
Filter front dimensions according EN 15805
Installation options
Disponibles cajones y marcos de acceso frontal y lateral.