Hi-Flo A, UF

  • Comprehensive range of standard sizes
  • Innovative pocket design for optimum air distribution
  • Conical pockets
  • Robust metal header frame
  • ICON2 eurovent energy efficiency class
  • ICON3 efficiency guarantee
  • ICON7 ISO16890.ai
  • ICON8
  • ICON31 Mount_bagfilters
  • ICON44 SGBC_
Item Type Model Name ISO/PM rating Filter Class EN779 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa) Yearly energy consumption at 3400m3/h Energy Class (Eurovent)
A5 ePM10 60% M5 592 592 600 3400 45 748 C
B5 ePM10 60% M5 490 592 600 2800 45 C
C7 ePM1 60% F7 287 592 600 1700 95 C
C5 ePM10 60% M5 287 592 600 1700 45 C
C6 ePM2,5 50% M6 287 592 600 1700 60 C
A6 ePM2,5 50% M6 592 592 600 3400 70 1189 C
B6 ePM2,5 50% M6 490 592 600 2800 60 C
A7 ePM1 60% F7 592 592 600 3400 95 1337 C
B7 ePM1 60% F7 490 592 600 2800 95 C
UH6 ePM2,5 50% M6 287 592 600 1700 55 B
UF6 ePM2,5 50% M6 592 592 600 3400 60 872 B
UG6 ePM2,5 50% M6 490 592 600 2800 55 B
UF9 ePM1 85% F9 592 592 600 3400 170 2130 D
UG9 ePM1 85% F9 490 592 600 2800 170 D
UH9 ePM1 85% F9 287 592 600 1700 170 D
UH7 ePM1 60% F7 592 592 600 3400 75 940 A
UG7 ePM1 60% F7 490 592 600 2800 75 A
UH7 ePM1 60% F7 287 592 600 1700 75 A
A8 ePM1 70% F8 592 592 600 3400 160
B8 490 592 600 2800 145
C8 ePM1 70% F8 287 592 600 1700 160
UF8 592 592 600 3400 110
UG8 490 592 600 2800 110
UH8 287 592 600 1700 110
3UF8 ePM1 70% F8 490 490 600 2334 145
 Pressure drop calculation tool is available

Calculate pressure drop

Choose a full-size filter module in the table above to calculate the pressure drop.
Full-size filter modules are typically 592x592mm for bag/panel filters and 610x610mm for HEPA filters.

Specifications

Application
Comfort air conditioning applications, pre filter applications
Frame
Galvanised steel
Media
Glass fiber
Max temperature °C
70°C
Relative Humidity
100%
Recommended final pressure drop, EN 13053
M5-F7: 200 Pa, F8-F9: 300 Pa
Dimension standard
Filter front dimensions according EN 15805
Installation options
Front and side access housings and frames are available
Max Airflow
1,25 x nominal flow
Call Auckland Office
+64 9 636 0663
Call Cambridge Office
+64 7 827 4142
Find a contact