Cam-Flo

  • Filter material of newly developed plastic fibre media
  • Low initial pressure loss, flat development
  • Newly-developed seam technique for better air distribution
  • Conical pockets and self-supporting bags
  • High mechanical strength
  • High dust holding capacity
  • Especially recommended for second stage filtration
  • ICON2 eurovent energy efficiency elass
  • ICON3 efficiency guarantee
  • ICON7 iso16890.ai
  • ICON31 Mount_bagfilters
ISO 16890 Filter Class EN779 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa) Energy (kWh/year) Energy Class (Eurovent)
ePM2,5 55% F7 287 592 640 1700 60 B
ePM2,5 55% F7 490 592 640 2800 60 B
ePM2,5 55% F7 592 592 640 3400 60 906 B
ePM2,5 55% F7 287 592 520 1700 75 C
ePM2,5 55% F7 490 592 520 2800 75 C
ePM2,5 55% F7 592 592 520 3400 75 1031 C
ePM2,5 55% F7 592 287 640 1700 60 B
ePM2,5 55% F7 592 490 640 2800 60 B
ePM2,5 55% F7 287 287 640 800 60 B
ePM2,5 55% F7 592 287 520 1700 75 C
ePM2,5 55% F7 592 490 520 2800 75 C
ePM2,5 55% F7 287 287 520 800 75 C
ePM1 75% F9 592 592 640 3400 105 1303 B
ePM1 75% F9 490 592 640 2800 105 B
ePM1 75% F9 287 592 640 1700 105 B
ePM1 75% F9 592 287 640 1700 105 B
ePM1 75% F9 592 490 640 2800 105 B
ePM1 75% F9 287 287 640 800 105 B
 Pressure drop calculation tool is available

Calculate pressure drop

Choose a full-size filter module in the table above to calculate the pressure drop.
Full-size filter modules are typically 592x592mm for bag/panel filters and 610x610mm for HEPA filters.

Specifications

Application
Air filtering in standard ventilation systems
Frame
Metal
Media
Synthetic
Max temperature °C
70ÂșC
Relative Humidity
90%
Max final pressure drop, EN 13053
Initial pressure drop + 100 Pa or initial pressure drop x3 (whichever is lower)
Dimension standard
Filter front dimensions according EN 15805
Installation options
Front and side access housings and frames are available
Max Airflow
1,25 x nominal flow