Cam-Flo

  • Filter material of newly developed plastic fibre media
  • Low initial pressure loss, flat development
  • Newly-developed seam technique for better air distribution
  • Conical pockets and self-supporting bags
  • High mechanical strength
  • High dust holding capacity
  • Especially recommended for second stage filtration
  • ICON2 eurovent energy efficiency class
  • ICON3 efficiency guarantee
  • ICON7 ISO16890.ai
  • ICON8
  • ICON31 Mount_bagfilters
ISO rating ISO 16890 Filter Class EN779 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa) Yearly energy consumption at 3400m3/h Energy Class (Eurovent)
ePM2,5 55% F7 287 592 640 1700 60 B
ePM2,5 55% F7 490 592 640 2800 60 B
ePM2,5 55% F7 592 592 640 3400 60 906 B
ePM2,5 55% F7 287 592 520 1700 75 C
ePM2,5 55% F7 490 592 520 2800 75 C
ePM2,5 55% F7 592 592 520 3400 75 1031 C
ePM2,5 55% F7 592 287 640 1700 60 B
ePM2,5 55% F7 592 490 640 2800 60 B
ePM2,5 55% F7 287 287 640 800 60 B
ePM2,5 55% F7 592 287 520 1700 75 C
ePM2,5 55% F7 592 490 520 2800 75 C
ePM2,5 55% F7 287 287 520 800 75 C
ePM1 75% F9 592 592 640 3400 105 1303 B
ePM1 75% F9 490 592 640 2800 105 B
ePM1 75% F9 287 592 640 1700 105 B
ePM1 75% F9 592 287 640 1700 105 B
ePM1 75% F9 592 490 640 2800 105 B
ePM1 75% F9 287 287 640 800 105 B
 Pressure drop calculation tool is available

Calculate pressure drop

Choose a full-size filter module in the table above to calculate the pressure drop.
Full-size filter modules are typically 592x592mm for bag/panel filters and 610x610mm for HEPA filters.

Specifications

Application
Air filtering in standard ventilation systems
Frame
Metal
Media
Synthetic
Max temperature °C
70ÂșC
Relative Humidity
90%
Recommended final pressure drop, EN 13053
F7: 200 Pa, F9: 300 Pa
Dimension standard
Filter front dimensions according EN 15805
Installation options
Front and side access housings and frames are available
Max Airflow
1,25 x nominal flow