CamGT 3V-600

  • Low air resistance (dP) for optimal economy
  • Ensures water drainage
  • High filtration efficiency
  • Low air resistance also in wet/ dry conditions
  • Solid HEPA frame eliminates air bypass
  • Resistant to high and extreme pressure drops
  • Suitable for all environment
  • ICON34 gasket_01_00_10
  • ICON3 efficiency guarantee
  • ICON5
  • ICON7 iso16890.ai
  • ICON9 en1822
  • ICON15 LCC optimized
ISO rating ISO 16890 Filter Class ASHRAE Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa)
ePM1 80% MERV 14 592 592 600 4250 100
ePM1 85% MERV 15 592 592 600 4250 115
MERV 16 592 592 600 4250 135
592 592 600 4250 140
592 592 600 4250 190
592 592 600 4250 190
592 592 600 4250 240
 Pressure drop calculation tool is available

Calculate pressure drop

m3/h
= Pa
Too high air flow for this filter

Specifications

Application
All installations where safety/reliability is crucial in combination with low air resistance
Frame
Plastic molded
Media
Glass fiber
Max temperature °C
70°C
Relative Humidity
100%
Recommended final pressure drop
600 Pa
Separator
Hot Melt
Gasket
Polyurethane, endless foamed
Grille, Downstream
Support grid for filtermedia
Sealant
Polyurethane
Max Airflow
1,8 x nominal flow
Comment
Burst strength: > 6250 Pa continuous wet/soaked.
Filter Class ASHRAE
MERV 16