CamPulse GTC

  • HemiPleat ™technology- proven open pleat solution
  • Non discharging F9
  • Water resistant media
  • Improved dust release
  • 2 in 1 package - saves space and money
  • Optimal ability to handle daily fog and humidity
  • Helicord design for efficient pulse cleaning
  • ICON5 Low Pressure Drop
  • ICON15 LCC optimized
  • ICON17 2in1
  • ICON54 ISO 29461 icon
Item Type ISO 29461 ISO/PM rating Filter Class EN779 Filter Class EN1822 Filter Class ASHRAE Diameter 1 (mm) Diameter 2 (mm) Length 1, Cylindrical (mm) Length 2, Cylindrical (mm) Airflow (m3/h) Pressure drop Initial (Pa)
Cyl/Cyl T9 ePM1 85% F9 MERV 15 445 324 660 660 2500 140
Co/Cyl T9 ePM1 85% F9 MERV 15 445/324 324 660 660 2500 165
Tenkay 34" ePM1 80% F9 MERV 15 324 864 1150 115
CyCy E10 MERV 15 324 445 660 660 2500 140
CoCy E10 MERV 15 324 445 660 660 2500 200

Specifications

Application
For humid/dry heavy dust load areas. Our recommended choice for one-stage self cleaning air intake systems
Filter Frame
Galvanised steel, Stainless steel
Media
Synthetic
Max temperature (°C)
70º C
Relative Humidity
100%
Recommended final pressure drop
1000 Pa
Pleat
HemiPleat
Separator
Hot-melt
Gasket
Polyurethane, endless foamed, EPDM
Sealant
Polyurethane
Max Airflow
1,1 x nominal flow
Comment
End caps: Available Galvanized steel (Standard), Powder coated, Stainless steel AISI304, Stainless steel AISI 31
Liners: External helical cords and internal screen, secure the filter element from movement without obstruction to the pulse
Additional information: Available in Co/Cy, Tenkay, and in other dimensions on request.
Filter Class ASHRAE
MERV 15

Articles related to Synthetic GTC

TurboPulse

The newest pulse technology for the 21st century, TurboPulse takes a modern approach to filter design with many new features engineered to improve filter life and pulse performance for turbomachinery.

Energy and Power Systems
It Can't Get Any Cleaner, or Can It?

Cartridge air intake filters improve gas turbine performance for union gas despite the very clean environment

A side by side comparison shows the benefits of higher grade GTC F9 gas turbine air intake filters for two RB211 gas turbines, even in very clean rural areas. It means a cleaner engine, higher power output, fewer water washes, and fuel savings.

Case studies Energy and Power Systems

Campulse gtc gas turbine air intake filters fighting fog, salt, and hydrocarbons for watson cogneration plant

The Watson Cogeneration Plant operates 4 GE, Frame 7EA engines and produces 400 MW for local refineries and sells excess electricity to the grid. The Plant Manager requested air intake efficiency, pressure drop, and water tests from Camfil. The test results revealed the true impact of the synthetic cartridge filters on gas turbine performance.

Case studies Energy and Power Systems