Megalam ProSafe

  • Globally most used Hepa panel
  • Long life time
  • Individually scantested
  • Prosafe certified:
  • Compliant to VDI 6022
  • Microbial inert components acc. to ISO 846
  • Tested for food safety acc. to EC 1935:2004
  • Free of bisphenol-A, phthalate and formaldehyde
  • Chemically resistant to inactivation and cleaning agent
  • Manufactured and packed in a controlled environment
  • ICON9 en1822
  • ICON20 prosafe
  • ICON42 UL logo
Item Type Filter Class EN1822 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa) Weight (kg)
Megalam MD15-1219x610-10/22 U15 1219 610 66 1205 145 8.92
Megalam MX15-914x610-10/22 U15 914 610 90 905 115 8.23
Megalam MX15-1219x610-10/22 U15 1219 610 90 1205 115 10.65
Megalam MG15-914x610-10/22 U15 914 610 110 905 80 9.42
Megalam MG15-1219x610-10/22 U15 1219 610 110 1205 80 12.19
Megalam MD14-914x610-10/22 H14 914 610 66 905 140 6.36
Megalam MD14-1219x610-10/22 H14 1219 610 66 1205 140 8.2
Megalam MX14-914x610-10/22 H14 914 610 90 905 95 7.62
Megalam MX14-1219x610-10/22 H14 1219 610 90 1205 95 9.83
Megalam MG14-914x610-10/22 H14 914 610 110 905 64 9.69
Megalam MG14-1219x610-10/22 H14 1219 610 110 1205 64 12.55
MD13- 305x610-10/22 H13 305 610 66 301 116 2,75
MD13- 610x610-10/22 H13 610 610 66 603 115 4,66
MD13- 914x610-10/22 H13 915 610 66 903 114 6,56
MD13- 1219x610-10/22 H13 1220 610 66 1205 114 8,47
MD13- 610x610x76-11/22 H13 610 610 78 603 118 10,38
Megalam MD13LS-305x610x71-10/22 H13 305 610 71 301 116 3.09
Megalam MD13LS-610x610x71-10/22 H13 610 610 71 603 115 3.09
Megalam MD13LS-914x610x71-10/22 H13 914 610 71 903 114 7.24
Megalam MD13LS-1219x610x71-10/22 H13 1219 610 71 1205 114 9.32
Megalam MD15-914x610-10/22 H13 914 610 66 903 145 6.9
Megalam MD14-305x610-10/22 H14 305 610 66 300 150 3,2
Megalam MD14-610x610-10/22 H14 610 610 66 600 140 5,4
Megalam MX14-305x610-10/22 H14 305 610 90 300 105 3,9
Megalam MX14-610x610-10/22 H14 610 610 90 605 95 6,5
Megalam MG14-305x610-10/22 H14 305 610 110 302 75 5,2
Megalam MG14-610x610-10/22 H14 610 610 110 605 65 8,6
Megalam MD15-305x610-10/22 U15 305 610 66 300 160 3,2
Megalam MD15-610x610-10/22 U15 610 610 66 600 150 5,4
Megalam MX15-305x610-10/22 U15 305 610 90 300 125 3,9
Megalam MX15-610x610-10/22 U15 610 610 90 605 115 6,5
Megalam MG15-305x610-10/22 U15 305 610 110 301 90 5,2
Megalam MG15-610x610-10/22 U15 610 610 110 603 80 8,6

Video

Specifications

Application
Hepa/ULPA filter for clean rooms and LAF benches
Frame
Anodized aluminium
Media
Glass fiber
Max temperature (°C)
70 °C
Relative Humidity
100%
Recommended final pressure drop
2x Initial pressure drop
Separator
Hot-melt
Gasket
Silicone Gel, Seamless PU foamed gasket
Grille, Downstream
Expanded metal painted (RAL 9010)
Grille, Upstream
Expanded metal painted (RAL 9010)
Sealant
Polyurethane
Max Airflow
Nominal flow rate (if not, efficiency drops)
Max. final pressure drop
MD: 500 Pa, MX: 600 pa, MG:800 Pa
Comment
All filter tested acc. to EN 1822 with individual protocol and packed in PE-film. Compliant with Prosafe** requirements. Other editions on request.

Related Products

Articles related to Megalam

Megalam EnerGuard

Camfils Megalam EnerGuard utilises the best features of all HEPA media types. EnerGuard incorporates the long life properties of glass fiber with the low energy consumption of membrane media to ensure optimal performance.

Life science and healthcare

HEPA FILTRATION-The Changing trends

HEPA filtration is required in a range of different Industries from Pharmaceuticals, Hospitals, Microelectronics and even the Food and Beverage Industry. Learn about the changing trends in HEPA filtration requirements, How HEPA filtration has advanced over the last number of years and how to identify and reduce the associated costs to your clean air requirements

Air quality Life science and healthcare