CleanSeal Integrity

Premium terminal HEPA filter housing for ceiling installation, with top-circular, side-circular or side-rectangular duct connection. Includes in-situ filter testing features for ISO14644 compliant aerosol injection. Suitable for turbulent supply airflow in Cleanrooms or other controlled environments. Open to customization.

  • Toolless filter clamping 100% secured and immediate
  • Built-in filter scaling option
  • Quick front plate locking for immediate access to the filter
  • Complete interchangeable diffusion front plates range
  • Robust fully welded construction for durable reliability and tightness
  • High corrosion protection against decontamination agents

Specifications

Application
Turbulent airflow in clean rooms and other controlled environments with ISO 14644-3 filter testing requirements, for ceiling installation.
Installation options
Universal mounting system for both suspended installation and compression mounting.
Comment
Construction: Steel, fully welded
Finish: Decontamination resistant double-layer powder coat
Standard color RAL 9010 (SW) or custom RAL
Option: Stainless steel SS 304 (S4) or SS 316L (S6)
Filter Gaskets: PU or GEL
Filters PU: MEGALAM MD(66mm)/(78mm)/MX(90mm)/MG(110mm)
Filters GEL: MEGALAM MD(71mm)/MX(105mm)/MG(115mm)
Control equipment: Room side accessible upstream pressure port concentration port and aerosol injection, plus +/- secondary ports for remote dp reading.
For more information about compatible filters and air diffuser front plates, see the relevant product pages
Option: Damper, adjustable from the room