CamCarb VG

  • Replacement items for Supply and Recirculation Air Systems in industrial applications.
  • May be filled with various molecular filtration medias, depending on the application and contaminant(s)
Item Type Pressure drop (Pa) Nominal weight (kg) Nominal weight (lbs) Optimum RH (%) Optimum temperature (°C) Optimum temperature (°F)
CamCarb VG300 Acids_H2Sᶺᶟ 315 14.5 32.0 40 - 90 10 - 60 50 - 140
CamCarb VG300 VOC 500 10.0 22.0 0 - 70 Max. 40 Max. 104
CamCarb VG300 H2S_Mercaptans 500 10.0 22.0 40 - 90 10 - 60 50 - 140
CamCarb VG300 Acids 500 10.0 22.0 40 - 90 10 - 60 50 - 140
CamCarb VG300 VOC_O3_Acids_TS 440 11.7 25.8 40 - 70 10 - 40 50 - 104
CamCarb VG300 VOC_O3_NO2_SO2 560 8.8 19.4 0 - 70 Max. 40 Max. 104
CamCarb VG300 Bases 500 10.0 22.0 40 - 90 10 - 40 50 - 104
CamCarb VG440 Bases 146 4.5 10.0 40 - 90 10 - 40 50 - 104
CamCarb VG300 SO2_H2Sᶺᶟ 315 14.5 32.0 40 - 90 10 - 60 50 - 140
CamCarb VG440 SO2_H2Sᶺᶟ 94 6.5 14.3 40 - 90 10 - 60 50 - 140
CamCarb VG440 Acids_H2Sᶺᶟ 94 6.5 14.3 40 - 90 10 - 60 50 - 140
CamCarb VG440 VOC 146 4.5 10.0 0 - 70 Max. 40 Max. 104
CamCarb VG440 H2S_Mercaptans 146 4.5 10.0 40 - 90 10 - 60 50 - 140
CamCarb VG440 Acids 146 4.5 10.0 40 - 90 10 - 60 50 - 140
CamCarb VG440 VOC_O3_Acids_TS 120 5.6 12.5 40 - 70 10 - 40 50 - 104
CamCarb VG440 VOC_O3_NO2_SO2 142 4.7 10.3 0 - 70 Max. 40 Max. 104

Specifications

Application
Heavy duty disposable plastic Vee Cell Modules to specifically treat corrosion control of electronic and electrical equipment in heavy process industries. They may also be used in odour removal applications in pulp and paper mills and wastewater treatment plants, or lighter applications such as airports, cultural heritage building and commercial offices.
Frame
ABS , PET
Media
Activated Carbon, Impregnated Activated Carbon, Impregnated Activated Alumina
Max temperature °C
-21ºC to 80ºC
Gasket
EPDM, PU-foam
Installation options
PSSA Housing, VG track
Comment
Filter performance will be affected if used in conditions where T and RH are above or below the optimum conditions.
VG300 can be used in Supply Air Systems, while the VG440 can be used in Supply Air and Recirculation Air Systems