Absolute CE

  • Range of standard sizes
  • Compact design
  • Very high efficiency
  • Hl3 are individually tested
  • ICON9 en1822
Filter Class EN1822 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Average (Pa)
E11 305 305 150 290 125
E11 457 457 150 660 125
E11 575 575 150 1055 125
E11 305 610 150 590 125
E11 610 610 150 1190 125
E11 762 610 150 1490 125
E11 914 610 150 1790 125
E11 1219 610 150 2380 125
E11 305 305 150 380 125
E11 457 457 150 865 125
E11 575 575 150 1385 125
E11 305 610 150 770 125
E11 610 610 150 1560 125
E11 762 610 150 1950 125
E11 914 610 150 2335 125
E11 1219 610 150 3120 125
E11 305 610 292 950 125
E11 457 610 292 1420 125
E11 610 610 292 1900 125
E11 762 610 292 2380 125
E11 305 610 292 1190 125
E11 457 610 292 1780 125
E11 610 610 292 2380 125
E11 762 610 292 2975 125

Specifications

Application
Very high efficiency final filtration in air conditioning systems housings-ducts or diffusers
Media
Glass fiber
Max temperature °C
70°C
Separator
Hot Melt
Gasket
Polyurethane, endless foamed
Installation options
Mounting systems: FCB Housings, Ducts, Diffusers, CAMSAFE
Max. final pressure drop
500 Pa
Comment
Fire rating: DIN 53438 Class Fl

Hospitals & Healthcare: St. James Hospital Dublin

Case Study: St James Hospital Prevents Aspergillus. Healthcare facilities must maintain the highest levels of cleanliness to promote health and healing. Camfil provides air cleaners for these environments. St. James Hospitaal in Dublin used Camfil for Aspergillus prevention.

Case Studies

Food & Beverage: World's Leading Beverage Company

Case Study: Clean Air For Leading Beverage Manufacturer. Air is the only ingredient involved in every aspect of food and beverage manufacturing. Air comes into contact with products from storage of goods all way to packaging. How can we help to keep your food processes safe?

UNIVERSITY SEES PROOF OF 24% LOWER ANNUAL ENERGY COSTS USING CAMFIL FILTER VS COMPETING FILTER

Case Study: Energy Savings At Western United States University. A Life Cycle Costing (LCC) analysis proved the Camfil Durafil filter operated at a 24% lower energy cost per year than the Viledon T-60. The Camfil product would save the customer $14 per filter per year versus the alternative.

Case Studies