Hi-Flo A, UF

  • Comprehensive range of standard sizes
  • Innovative pocket design for optimum air distribution
  • Conical pockets
  • Robust metal header frame
  • ICON2 eurovent energy efficiency class
  • ICON3 efficiency guarantee
  • ICON7 ISO16890.ai
  • ICON8
  • ICON21 P mark
  • ICON31 Mount_bagfilters
  • ICON44 SGBC_
Item Type ISO/PM rating Filter Class EN779 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa) Yearly energy consumption at 3400m3/h Energy Class (Eurovent)
A5 ePM10 60% M5 592 592 600 3400 45 748 C
B5 ePM10 60% M5 490 592 600 2800 45 C
C7 ePM1 60% F7 287 592 600 1700 95 C
C5 ePM10 60% M5 287 592 600 1700 45 C
C6 ePM2,5 50% M6 287 592 600 1700 60 C
A6 ePM2,5 50% M6 592 592 600 3400 70 1189 C
B6 ePM2,5 50% M6 490 592 600 2800 60 C
A7 ePM1 60% F7 592 592 600 3400 95 1337 C
B7 ePM1 60% F7 490 592 600 2800 95 C
UH6 ePM2,5 50% M6 287 592 600 1700 55 B
UF6 ePM2,5 50% M6 592 592 600 3400 60 872 B
UG6 ePM2,5 50% M6 490 592 600 2800 55 B
3UF6 ePM2,5 50% M6 490 490 600 2334 70 B
UF9 ePM1 85% F9 592 592 600 3400 170 2130 D
UG9 ePM1 85% F9 490 592 600 2800 170 D
UH9 ePM1 85% F9 287 592 600 1700 170 D
UH7 ePM1 60% F7 592 592 600 3400 75 940 A
UG7 ePM1 60% F7 490 592 600 2800 75 A
UH7 ePM1 60% F7 287 592 600 1700 75 A
3UF7 ePM1 70% F7 490 490 600 2334 115 B
A8 ePM1 70% F8 592 592 600 3400 160
B8 ePM1 70% F8 490 592 600 2800 160
C8 ePM1 70% F8 287 592 600 1700 160
UF8 ePM1 70% F8 592 592 600 3400 145
UG8 ePM1 70% F8 490 592 600 2800 145
3UF8 ePM1 70% F8 490 490 600 2334 145
UH8 F8 287 592 600 1700 145
 Pressure drop calculation tool is available

Calculate pressure drop

m3/h
= Pa
Too high air flow for this filter

Specifications

Application
Comfort air conditioning applications, pre filter applications
Frame
Galvanised steel
Media
Glass fiber
Max temperature °C
70°C
Relative Humidity
100%
Max final pressure drop, EN 13053
Initial pressure drop + 100 Pa or initial pressure drop x3 (whichever is lower)
Dimension standard
Filter front dimensions according EN 15805
Installation options
Front and side access housings and frames are available
Max Airflow
1,25 x nominal flow