
กรณีศึกษานี้เน้นย้ำถึงการประหยัดพลังงานที่เพิ่มขึ้นผ่านการใช้งานตัวกรอง Hi-Flo XLT และ 30/30
20,000 euro saved due to longer lasting filters
10,000 euro saved in energy consumption by choosing A+ filters
Less labour, waste disposal and operational cost


Frequent changes of their prefiltration was a key problem. The panel filters previously used were only able to be operational for one month before they would become saturated
The secondary filters stage was causing a high pressure drop in the AHU which created higher energy consumption within the system
The location of the datacentre meant that the filters would be exposed to high levels of dust concentrations. This meant that a high dust holding capacity of the filter would be needed
After the start-up, an external company performed an analysis to determine the effectiveness of the installation in both rooms. The measurements were carried out according to the ISO 14644-3:2021 standard for the average value of particles sizes 0.5 μm (number of particles) and 5 μm (particles/m³). The results obtained showed that not only is the ISO 8 class reached, but the values are at the limit of the ISO 7 class (the concentration of particles between one class and the next is 10 times lower).
Likewise, the active control of the CC 6000 equipment through the AirImage sensor represents an energy saving that allows the client to reduce the operating cost of the installation and contribute positively to the environment.
Increased durability and dustretention capacity in the filters.
Considerable reduction in pressure drop.
Reduced waste generation.
Decreased energy consumption.
Carbon footprint reduction.
Lower operational costs.
Improved and assured indoor air quality.
Client loyalty, providing us with the opportunity to implement these changes in other data centres.