City-Flo XL

  • Combined particle and molecular filter
  • Low initial pressure drop
  • Conical pockets
  • Moulded, rigid and aerodynamic shaped plastic frame
  • ICON2 eurovent energy efficiency elass
  • ICON3 efficiency guarantee
  • ICON6
  • ICON7 iso16890.ai
  • ICON21 P mark
  • ICON25 ozone 3
  • ICON31 Mount_bagfilters
  • ICON37 ISO10121
  • ICON45 HAZE FREE
ISO/PM rating Filter Class EN779 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa) Energy (kWh/year) Energy Class (Eurovent)
ePM1 60% F7 490 592 520 2700 110 C
ePM1 60% F7 287 592 520 1700 110 C
ePM1 60% F7 592 592 520 3400 110 1405 C
ePM1 60% F7 490 490 640 2330 85 B
ePM1 60% F7 592 490 640 2700 85 B
ePM1 60% F7 592 287 640 1700 85 B
ePM1 60% F7 287 287 640 800 85 B
ePM1 60% F7 287 592 640 1700 85 B
ePM1 60% F7 490 592 640 2700 85 B
ePM1 60% F7 592 592 640 3400 85 1087 B
ePM1 60% F7 287 287 520 800 110 C
ePM1 60% F7 592 287 520 1700 110 C
ePM1 60% F7 592 490 520 2700 110 C
ePM1 60% F7 490 490 520 2330 110 C
 Pressure drop calculation tool is available

Calculate pressure drop

Choose a full-size filter module in the table above to calculate the pressure drop.
Full-size filter modules are typically 592x592mm for bag/panel filters and 610x610mm for HEPA filters.

Specifications

Application
Particulate and molecular filter
Frame
Plastic moulded
Media
Glass fiber/Activated carbon
Max temperature °C
50ÂșC
Relative Humidity
70%
Max final pressure drop, EN 13053
Initial pressure drop + 100 Pa or initial pressure drop x3 (whichever is lower)
Dimension standard
Filter front dimensions according EN 15805
Installation options
Front and side access housings and frames are available
Max Airflow
1,25 x nominal flow
Call Camfil Middle East Regional Office!
Find a contact