Absolute CM

  • Compact design concept
  • Very high efficiency
  • Incinerable
  • Scannable
  • ICON9 en1822
Item Type Filter Class EN1822 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa)
CMD11-305x305x150-PO E11 305 305 150 236 125
CMD11-457x457x150-PO E11 457 457 150 580 125
CMD11-305x610x150-PO E11 305 610 150 505 125
CDM11-610x610x150-PO E11 610 610 150 1080 125
CMD11-762x610x150-PO E11 762 610 150 1370 125
CMD11-914x610x150-PO E11 914 610 150 1650 125
CMD11-1219x610x150-PO E11 1219 610 150 2220 125
CMX11-305x305x150-PO E11 305 305 150 310 125
CMX11-457x457x150-PO E11 457 457 150 760 125
CMX11-575x575x150-PO E11 575 575 150 1245 125
CMX11-305x610x150-PO E11 305 610 150 668 125
CMX11-610x610x150-PO E11 610 610 150 1410 125
CMX11-762x610x150-PO E11 762 610 150 1788 125
CMX11-914x610x150-PO E11 914 610 150 2150 125
CMX11-1219x610x150-PO E11 1219 610 150 2900 125
CMG11-305x610x292-PO E11 305 610 292 815 125
CMG11-457x610x292-PO E11 457 610 292 1265 125
CMG11-610x610x292-PO E11 610 610 292 1735 125
CMG11-762x610x292-PO E11 762 610 292 2180 125
CMT11-305x610x292-PO E11 305 610 292 1015 125
CMT11-457x610x292-PO E11 457 610 292 1585 125
CMT11-610x610x292-PO E11 610 610 292 2170 125
CMT11-762x610x292-PO E11 762 610 292 2725 125

Specifications

Application
HEPA filter for standard applications
Frame
MDF
Media
Glass fiber
Max temperature °C
70ºC
Relative Humidity
100%
Recommended final pressure drop
2x Initial pressure drop
Separator
Hot Melt
Gasket
Polyurethane, endless foamed
Sealant
Polyurethane
Max. final pressure drop
800 Pa
Comment
Remarks: All filters scan tested acc. EN 1822
Other options available: Galvanized frame
Fire rating: DIN 53438 Class Fl

Articles related to Absolute™ C, D

Hospitals & Healthcare: St. James Hospital Dublin

Case Study: St James Hospital Prevents Aspergillus. Healthcare facilities must maintain the highest levels of cleanliness to promote health and healing. Camfil provides air cleaners for these environments. St. James Hospitaal in Dublin used Camfil for Aspergillus prevention.

Case Studies

Food & Beverage: World's Leading Beverage Company

Case Study: Clean Air For Leading Beverage Manufacturer. Air is the only ingredient involved in every aspect of food and beverage manufacturing. Air comes into contact with products from storage of goods all way to packaging. How can we help to keep your food processes safe?

Camtain® Contains Explosive Pharma Dust

Case Study: Camtain Contains Explosive Pharma Dust. A multinational pharmaceutical company needed a dust extraction system for their new tableting suite in Spain. The suite comprised of six rooms, each with its own tablet machine that created explosive dusts.

Case Studies

UNIVERSITY SEES PROOF OF 24% LOWER ANNUAL ENERGY COSTS USING CAMFIL FILTER VS COMPETING FILTER

Case Study: Energy Savings At Western United States University. A Life Cycle Costing (LCC) analysis proved the Camfil Durafil filter operated at a 24% lower energy cost per year than the Viledon T-60. The Camfil product would save the customer $14 per filter per year versus the alternative.

Case Studies

SCHOOL LEARNS THE BENEFIT OF FRESH AIR

Case Study: School Learns the Benefit of Clean Air. Camfil worked with a school to help improve the indoor air quality for students during the critical exam period. They provided the school with Camfil air purifiers for use in their gymnasium where students sit their exams.

Case Studies

Call Camfil Middle East Regional Office!
Find a contact