Closepleat MXS

HEPA H13 & H14 filter for supply & exhaust air systems that require basic Hepa level of protection. The filter are used in systems with basic air velocities (up to 1,5 m/s). High quality MDF frame eases waste handling through full incinerability.

  • Basic Panel Type Hepa Filter.
  • Low to medium airflow (up to 1,5 m/s)
  • Completely incinerable, no metal used
  • 100% leak-free, individually scan tested.
  • ICON9 en1822
Item Type Filter Class EN1822 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa)
MXS13-305x305x78-1PU H13 305 305 78 310 250
MXS13-457x457x78-1PU H13 457 457 78 760 250
MXS13-575x575x78-1PU H13 575 575 78 1245 250
MXS13-305x610x78-1PU H13 305 610 78 660 250
MXS13-610x610x78-1PU H13 610 610 78 1500 250
MXS13-762x610x78-1PU H13 762 610 78 1790 250
MXS13-915x610x78-1PU H13 915 610 78 2160 250
MXS13-1220x610x78-1PU H13 1220 610 78 2910 250
MXS13-305x305x150-1PU H13 305 305 150 310 250
MXS13-457x457x150-1PU H13 457 457 150 760 250
MXS13-575x575x150-1PU H13 575 575 150 1245 250
MXS13-305x610x150-1PU H13 305 610 150 660 250
MXS13-610x610x150-1PU H13 610 610 150 1500 250
MXS13-762x610x150-1PU H13 762 610 150 1790 250
MXS13-915x610x150-1PU H13 915 610 150 2160 250

Specifications

Application
Final HEPA Filtration for terminal housings
Filter Frame
MDF
Media
Glass fiber
Max temperature (°C)
70ºC
Relative Humidity
100%
Recommended final pressure drop
2x Initial pressure drop
Separator
Hot-melt
Gasket
Polyurethane, endless foamed
Sealant
Polyurethane
Max Airflow
Can be calculated on request
Max. final pressure drop
600 Pa
Comment
All filter tested acc. to EN 1822 with individual protocol.

Articles related to Closepleat