EcoPleat G

A pleated panel filter with plastic frame suitable for environments with high humidities. With its low pressure drop and high dust holding capacity, lowest labour cost thanks to less frequent filter changes can be achieved. This filter comes in ePM1 as well as ePM10 efficiencies according to ISO16890.

  • Ultra compact panel filter with ePM1 and ePM10 efficiencies
  • Low pressure drop thanks to large surface area
  • Long operating life with large dust holding capacity
  • Less frequent changes
  • Fully combustible plastic frame
  • ICON3 efficiency guarantee
  • ICON7 iso16890.ai
  • ICON42 UL logo
Item Type ISO/PM rating Filter Class EN779 Filter Class ASHRAE Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa)
3GPPS-12242-M6 ePM10 70% M6 MERV 11 287 592 48 950 50
3GPPS-20242-M6 ePM10 70% M6 MERV 11 490 592 48 1500 50
3GPPS-24242-M6 ePM10 70% M6 592 592 48 2900 75
3GPPS-12242-F7 ePM1 55% F7 287 592 48 1450 110
3GPPS-20242-F7 ePM1 55% F7 MERV 13 490 592 48 1500 75
3GPPS-24242-F7 ePM1 55% F7 592 592 48 2900 110
3GPPS-12242-F8 ePM1 70% F8 287 592 48 1450 160
3GPPS-20242-F8 ePM1 70% F8 MERV 14 490 592 48 1500 85
3GPPS-24242-F8 ePM1 70% F8 592 592 48 2900 160
3GPPS-12244-M6 ePM10 70% M6 287 592 96 1450 70
3GPPS-20244-M6 ePM10 70% M6 MERV 11 490 592 96 2800 105
3GPPS-24244-M6 ePM10 70% M6 592 592 96 2900 70
3GPPS-12244-F7 ePM1 55% F7 287 592 96 1450 100
3GPPS-20244-F7 ePM1 55% F7 MERV 13 490 592 96 2800 135
3GPPS-24244-F7 ePM1 55% F7 592 592 96 2900 100
3GPPS-12244-F8 ePM1 70% F8 287 592 96 1450 105
3GPPS-20244-F8 ePM1 70% F8 MERV 14 490 592 96 2800 145
3GPPS-24244-F8 ePM1 70% F8 592 592 96 2900 105
3GPPS-24244-F9 ePM1 80% F9 MERV 15 592 592 96 3400 160
3GPPS-12244-F9 ePM1 80% F9 MERV 15 287 592 96 1700 160
3GPPS-20244-F9 ePM1 80% F9 MERV 15 490 592 96 2800 160
 Pressure drop calculation tool is available

Calculate pressure drop

Choose a full-size filter module in the table above to calculate the pressure drop.
Full-size filter modules are typically 592x592mm for bag/panel filters and 610x610mm for HEPA filters.

Specifications

Application
Air conditioning or industrial processing systems and for mini air conditioning systems, individual modules, ventilation equipment
Filter Frame
ABS
Media
Glass fiber
Max temperature (°C)
70ÂșC
Relative Humidity
100%
Separator
Hot-melt
Dimension standard
Filter front dimensions according EN 15805
Installation options
Front and side access housings and frames are available.
Max Airflow
1,1 x nominal flow
Max. final pressure drop
350 Pa
Filter Class ASHRAE
MERV 14

Related Products

Articles related to EcoPleat

world leading online marketplace for vacation rentals TRUSTS CAMFIL solutions at its workplace in india

With the increase in indoor air pollution in India and its association with an increased number in morbidity and mortality, measures include accessing the exposure levels of the indoor air pollutants and using the right air filtration solutions.

Case Studies Commercial and Public buildings Air quality
Call Auckland Office
+64 9 636 0663
Call Cambridge Office
+64 7 827 4142
Find a contact