CityPleat

Premium prefilter with a particulate and molecular media to remove solid and gaseous contaminants in one filter stage. It can be used in existing installations to remove low concentrations of most external and internal pollutants with Coarse 60% efficiency according to ISO16890.

  • “2-in-1” filtration solution; particulate and molecular
  • Removal of solid and gaseous contaminants in one filter stage
  • Ideal for filtering low concentrations of most external and internal source pollutants
  • Can be used to upgrade existing installations
  • ICON6 Molecular
  • ICON7 iso16890.ai
  • ICON26 ozone 5
  • ICON27 ozone 6
  • ICON37 ISO10121
Item Type ISO/PM rating Filter Class EN779 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa)
CityPleat-100-594x594x44 Coarse 65% G4 594 594 44 2000 140
CityPleat-100-289x594x44 Coarse 65% G4 289 594 44 1000 140
CityPleat-200-289x594x44 Coarse 65% G4 289 594 44 1700 140
CityPleat-200-594x594x44 Coarse 65% G4 594 594 44 3400 140
CityPleat-200-594x594x95 Coarse 65% G4 594 594 95 3400 125
CityPleat-200-289x594x95 Coarse 65% G4 289 594 95 1700 125
CityPleat-480-594x594x95 Coarse 65% G4 594 594 95 3400 90
CityPleat-480-289x594x95 Coarse 65% G4 289 594 95 1700 90

Specifications

Application
High efficiency particle filtration for deodarisation and removal of gas pollutants, used for filtration in offices, airports
Filter Frame
Water resistant cardboard
Media
Synthetic/Activated Carbon
Max temperature (°C)
50ºC
Relative Humidity
30% - 70%
Max final pressure drop, EN 13053
Initial pressure drop + 50 Pa or initial pressure drop x3 (whichever is lower)
Dimension standard
Filter front dimensions according EN 15805
Installation options
Front and side access housings and frames are available
Max Airflow
1,25 x nominal flow
Max. final pressure drop
250 Pa
Comment
Ozone removal efficiency: 50 - 70% depending on model and air flow. All values are +-15%

Related Products

Articles related to CityPleat

Can We Remove it

Dealing with airborne odours, toxins and gases can be a big challenge. Learn about how Molecular Contamination Control and how it can protect against the harmful effects of these airborne contaminants.

Manufacturing and Machinery Commercial and Public buildings Electronics and optics Life science and healthcare Air quality Food and beverage Education and Experience
Call Kuala Lumpur Office
+603 8023 8250
Call Penang Office
+604 642 5004
Find a contact