30/30

The 30/30 pleated panel filter is ideal for first-stage filtration to protect bag filters or V-Bank filters, and to keep the HVAC system clean. With its large media area, it provides a prolonged lifetime and reduces the number of panel filter changes, making it a great sustainable filter choice.

  • Sustainable moisture-resistant cardboard frame with diagonal front and back lattice for extra support.
  • Prefilter ePM10 50%
  • Optimized energy efficiency
  • Long lifetime - up to 6 months depending on the application
  • Increased media area for high dust holding capacity and prolonged lifetime.
  • Radial pleats supported by a metal grid hold the pleat formation throughout its lifetime
  • ICON7 iso16890.ai
  • ICON23 Eurovent_no_abc
  • ICON42 UL logo
Item Type ISO 16890 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa) Energy (kWh/year) Energy Class (Eurovent)
1050 595x595x46 ePM10 50% 595 595 46 3400 70 >1100 E
1050 493x493x46 ePM10 50% 493 493 46 2400 70 E
1050 493x622x46 ePM10 50% 493 622 46 3000 70 E
1050 493x595x46 ePM10 50% 493 595 46 2800 70 E
1050 393x622x46 ePM10 50% 393 622 46 2400 70 E
1050 393x493x46 ePM10 50% 393 493 46 1900 70 E
1050 289x595x46 ePM10 50% 289 595 46 1700 70 E
1050 595x595x95 ePM10 50% 595 595 95 3400 65 1098 D
1050 493x493x95 ePM10 50% 493 493 95 2400 65 D
1050 493x622x95 ePM10 50% 493 622 95 3000 65 D
1050 493x595x95 ePM10 50% 493 595 95 2800 65 D
1050 393x622x95 ePM10 50% 393 622 95 2400 65 D
1050 393x493x95 ePM10 50% 393 493 95 1900 65 D
1050 289x595x95 ePM10 50% 289 595 95 1700 65 D
 Pressure drop calculation tool is available

Calculate pressure drop

Choose a full-size filter module in the table above to calculate the pressure drop.
Full-size filter modules are typically 592x592mm for bag/panel filters and 610x610mm for HEPA filters.

Specifications

Application
Prefilter for air conditioning systems
Filter Frame
Rigid water resistant cardboard
Media
Synthetic
Max temperature (°C)
90ยบ C
Relative Humidity
100%
Max final pressure drop, EN 13053
Initial pressure drop + 100 Pa or initial pressure drop x3 (whichever is lower)
Dimension standard
Filter front dimensions according EN 15805
Installation options
Front and side access housings and frames are available
Max Airflow
1,25 x nominal flow

Related Products

Articles related to 30/30

Benefits of premium prefilters

Choosing the right prefilter for optimal performance

Choosing the right prefiltration strategy can optimize the performance of your ventilation system and reduce your environmental impact.

Commercial and Public buildings Air quality

Grocery Store Case Study USA

Premium air filters help global grocer significantly improve air quality and reduce maintenance costs, waste and storage

Case Studies

Dairy Processing Facility USA

Case Study: Dual 9 air filter. Higher performance, extended life (3-4 times longer), lower total cost and increased containment collection.

Case Studies Food and beverage

Air Quality recommendations for hotels

Air quality has always been an important factor for hotels, whether it has been removing odours from kitchen extracts to ensuring a clean environment by reducing particulate levels.

Commercial and Public buildings Air cleaners and air purifiers Virus Contamination Control Air quality

Camfil Serves Up Savings in Energy, Filter Costs, and Labour

Case Study: Filter Savings At Frozen Food Manufacturer. Three air handling units supplied air to critical processing areas in one of the USA's largest frozen food manufacturing facilities. The pre and final filter combination saved the plant over $33,000 per year.

Case Studies

Global Leader In Beverage Industry Cuts Annual Filter Use By More Than 80 Percent

Case Study: Bottled Water Producer Reduces Labour And Waste. One of the largest global food companies and a global leader in the bottled water industry, read about how this company turned to Camfil to help meet its strong commitment to health, hydration and the environment in particular.

Case Studies

Clean Air Requirements? Contact us today!
Find a contact