Absolute VGHF

Compact HEPA filter with header frame for air handling units that require a very high airflow and low pressure drop. Modern plastic frame with V-shaped pleat pack arrangement combines high capacity with low pressure drop and weight.

  • High airflow (up to 2,3m/s).
  • Compact HEPA filter with header frame
  • Completely incinerable
  • Easy Hepa upgrade of AHU
  • ICON9 en1822
Item Type Filter Class EN1822 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa)
VGHF10-592X287X300 E10 592 287 300 1700 250
VGHF10-592X490X300 E10 592 490 300 2850 250
VGHF10-592X592X300 E10 592 592 300 4000 250
VGHF13-592x287x300-OP-S H13 592 287 300 1350 250
VGHF13-592x490x300-OP-S H13 592 490 300 2450 250
VGHF13-592x592x300-OP-S H13 592 592 300 3000 250

Specifications

Application
EPA/HEPA final filtration in air conditioning systems and industrial processes
Filter Frame
ABS; header frame, 25mm
Media
Glass fiber
Max temperature (°C)
70ºC
Relative Humidity
100%
Recommended final pressure drop
2x Initial pressure drop
Separator
Hot-melt
Gasket
Polyurethane, endless foamed, Flat gasket
Sealant
Polyurethane
Installation options
Front and side access housings and frames are available. Type 8 and FC housings.
Max Airflow
Nominal flow rate (if not, efficiency drops)
Max. final pressure drop
500 Pa
Comment
All filter auto-tested acc. EN 1822 and individually packed in PE-foil. Other editions on request